Bus bar connections are critical in electrical installations. I want to clarify some items in the May “Back to Basics” article. Most bus bars are silver or tin-plated—not copper plated. The purpose of plating is to reduce oxidation, thus improving the connections. This thin plating can scrape off easily. Abrasive cleaning will likely remove the plating, leading to hot joints and potential failure.